Inspection During and Immediately After System Pressure Tests

WARNING: EXTREME CARE MUST BE EXERCISED WHILE INSPECTING ANY PRESSURIZED SYSTEM OR COMPONENT.

A visual inspection of the system shall include checking for the following.

  • Evidence of leakage or loss of pressure.

  • Distortion or yielding of anchors, pipe expansion joint hardware, the bellows, and other piping components.

  • Any unanticipated movement of the piping due to pressure.Evidence of instability (squirm) in the bellows.

  • The guides, pipe expansion joints, and other moveable parts of the system shall be inspected for evidence of binding.

  • Any evidence of abnormality or damage shall be reviewed and evaluated by a competent design authority.